Many Bay Area condos and apartments have a First Co. air handler hung in the ceiling, and the same complaint: water dripping from the unit, or a stain spreading across the ceiling below it.
Open one up and you'll often feel air rushing at the side of the cabinet, with water running down the side wall, outside the drain pan. The pan may not be broken. The water can be carried around it.
First rule out a clogged drain, a freezing coil, and a unit that isn't level. If none of those is the issue, check the following before replacing the pan.
See it happen
This is the fan coil above your ceiling. The copper U-bends stick out of the left end, over the drain pan. Flip the switch to see the problem and the fix.
Why the U-bends cause the leak
The coil's fins guide water straight down into the pan. The copper U-bends at the end don't. They're smooth, and they sit outside the fins, next to the cabinet wall.
The blowers push air through the coil, so the coil box is under pressure. If there's an unsealed gap at the coil end plate, that pressure forces a fast jet of air out across the U-bends. It strips the drops off sideways and carries them past the edge of the pan.
What we think can help the tech fix the issue (only for trained HVAC technicians)
Homeowners: don't open the unit yourself; it has live electrical parts and refrigerant inside. Share this page with your tech, or call us.
Recommended materials
- UL 181A-P or 181B-FX foil tape: flat metal seams and access panels. Not fabric duct tape; it dries out and cracks.
- Water-based duct mastic: irregular joints and permanent seams.
- Fiberglass mesh tape: bridges gaps wider than 1/4" under mastic.
- Closed-cell foam or neoprene tape (about 1/2" × 1/4"): the end plate and the access door flange. Not open-cell foam; it soaks up water.
Step by step
Power off and clean. Wipe the end plate, cabinet seams, and duct collar with isopropyl alcohol or degreaser.
Verify: a clean cloth picks up no residue.
Seal the end-plate gap. Line the gap between the end plate and the cabinet with closed-cell neoprene so pressure can't force air across the U-bends.
Verify: the gasket is continuous with no visible gap.
Gasket the service door. Put closed-cell foam on the door frame's inner lip instead of mastic, then refit the factory screws.
Verify: the foam compresses evenly and the panel sits flush.
Seal cabinet seams and duct joints. Foil tape for seams under 1/4", squeegeed flat. Wider gaps get mesh tape, then mastic at least nickel-thick, 1" past each side.
Verify: a continuous seal with no lifted edges or pinholes.
Check the drain and slope. Flush the drain. Confirm the unit and condensate drain are installed with the slope required by the manufacturer and applicable code.
Verify: the pan drains fully.
What you can check yourself
- Change a dirty filter. It starves the coil of airflow and can make condensation problems worse.
- Keep supply vents open. Closed or blocked vents raise the pressure in the coil box and make this leak worse.
- Water on the ceiling? Turn the AC off until it's checked. Wet drywall can come down.
- A cracked pan is one possible cause. But if water is being carried around the pan rather than leaking through it, replacing the pan may not solve the problem.
The short version
Pressure forces air out an open gap beside the U-bends, strips the water off, and carries it past the pan. Seal the gap and keep the supply vents open, and the water drains where it should.
Three other leaks, three other causes: AC leaking water? It's usually not the drip pan.