Many Bay Area condos and apartments have a First Co. air handler hung in the ceiling, and the same complaint: water dripping from the unit, or a stain spreading across the ceiling below it.

Open one up and you'll often feel air rushing at the side of the cabinet, with water running down the side wall, outside the drain pan. The pan may not be broken. The water can be carried around it.

First rule out a clogged drain, a freezing coil, and a unit that isn't level. If none of those is the issue, check the following before replacing the pan.

See it happen

This is the fan coil above your ceiling. The copper U-bends stick out of the left end, over the drain pan. Flip the switch to see the problem and the fix.

Ceiling fan coil: bypass air blasts across the U-bends and pushes the water to the side wallThree-quarter view of a horizontal ceiling fan coil: a flat top plate with mounting tabs, two round blower housings in front, copper U-bends on the left end above the drain pan extension, and refrigerant lines off the right end. Warm return air, drawn red, is pulled into the blowers, pushed through the coil, and blown out the back of the coil to the rooms as cool air, drawn blue, so the coil box is under pressure. Some bypass air slips out of the coil box through unsealed openings around the tube holes, where the U-bend tubes pass through the end plate, blasts across the sweating U-bends, pushes the water drops onto the side of the ceiling box past the edge of the drain pan, and is then sucked into the side of the left blower. The water runs down the wall and stains the drywall ceiling.+++Blowers push air through the coil (+)so the coil box is under pressureUnsealed tube holesair escapes around the tubes hereIt blasts across the U-bendsand pushes the water to the side wallWater runs down the wall,past the edge of the panSide of the ceiling boxThen it's sucked intothe side of the blowerCeiling stainSame pressure in the coil box (+)Now the air can only go through the finsDuct sealant covers the tube holesWater drips straightdown into the panCeiling stays dryRefrigerant linesBlower wheelspush air through the coilDrain pan extensionunder the U-bends, with the drain stubCool air outblown out the back of the coilWarm return air inpulled intothe blowers
Red is the warm return air coming in. Blue is the cooled air. Watch the cool stream that takes a shortcut out around the tubes, right across the U-bends. The copper U-bends on the end of the coil sit outside the fins, and they sweat like the rest of the coil. That water is supposed to drip straight down into the pan extension. When the holes where the tubes pass through the end plate aren't sealed, air slips out of the coil box, blasts across the bends, pushes the drops onto the side wall past the edge of the pan, and is then sucked into the side of the blower. Seal the tube holes with duct sealant, and the water falls where it's supposed to.

Why the U-bends cause the leak

The coil's fins guide water straight down into the pan. The copper U-bends at the end don't. They're smooth, and they sit outside the fins, next to the cabinet wall.

The blowers push air through the coil, so the coil box is under pressure. If there's an unsealed gap at the coil end plate, that pressure forces a fast jet of air out across the U-bends. It strips the drops off sideways and carries them past the edge of the pan.

What we think can help the tech fix the issue (only for trained HVAC technicians)

Homeowners: don't open the unit yourself; it has live electrical parts and refrigerant inside. Share this page with your tech, or call us.

Recommended materials

  • UL 181A-P or 181B-FX foil tape: flat metal seams and access panels. Not fabric duct tape; it dries out and cracks.
  • Water-based duct mastic: irregular joints and permanent seams.
  • Fiberglass mesh tape: bridges gaps wider than 1/4" under mastic.
  • Closed-cell foam or neoprene tape (about 1/2" × 1/4"): the end plate and the access door flange. Not open-cell foam; it soaks up water.

Step by step

  1. Power off and clean. Wipe the end plate, cabinet seams, and duct collar with isopropyl alcohol or degreaser.

    Verify: a clean cloth picks up no residue.

  2. Seal the end-plate gap. Line the gap between the end plate and the cabinet with closed-cell neoprene so pressure can't force air across the U-bends.

    Verify: the gasket is continuous with no visible gap.

  3. Gasket the service door. Put closed-cell foam on the door frame's inner lip instead of mastic, then refit the factory screws.

    Verify: the foam compresses evenly and the panel sits flush.

  4. Seal cabinet seams and duct joints. Foil tape for seams under 1/4", squeegeed flat. Wider gaps get mesh tape, then mastic at least nickel-thick, 1" past each side.

    Verify: a continuous seal with no lifted edges or pinholes.

  5. Check the drain and slope. Flush the drain. Confirm the unit and condensate drain are installed with the slope required by the manufacturer and applicable code.

    Verify: the pan drains fully.

What you can check yourself

  • Change a dirty filter. It starves the coil of airflow and can make condensation problems worse.
  • Keep supply vents open. Closed or blocked vents raise the pressure in the coil box and make this leak worse.
  • Water on the ceiling? Turn the AC off until it's checked. Wet drywall can come down.
  • A cracked pan is one possible cause. But if water is being carried around the pan rather than leaking through it, replacing the pan may not solve the problem.

The short version

Pressure forces air out an open gap beside the U-bends, strips the water off, and carries it past the pan. Seal the gap and keep the supply vents open, and the water drains where it should.

Three other leaks, three other causes: AC leaking water? It's usually not the drip pan.

Ceiling unit leaking in the East Bay or the Tri-Valley? We'll find the cause before we sell you a part.