R-454B Pressure-Temperature Chart

Click the saturation curve, edit a value, or scan the table — every view stays in sync. Manufacturer-sourced bubble-point data for R-410A's lower-GWP successor.

For Licensed & Trained HVAC Technicians Only

This checklist is intended exclusively for use by licensed, certified, and trained HVAC professionals. It is not a DIY guide and should not be used by untrained individuals to perform repairs or diagnostics. The purpose of this checklist is to help qualified technicians maintain a consistent, step-by-step workflow so that no critical step is overlooked or skipped during service.

R-454B Saturation Curve

R-32 / R-1234yf (68.9 / 31.1 by mass, A2L) — zeotropic blend, ~1.5 °F glide

Units
020406080100120140Temperature (°F)050100150200250300350400450500550600650Pressure (psig)

Click or tap anywhere on the chart — the cursor snaps to the R-454B saturation curve and stays there until your next click.

Direct Lookup

Edit either field — the other updates instantly. The chart cursor moves in sync.

Lookup Table

Tap any row to highlight that point on the chart.

Temp (°F)Pressure (psig)
045.3
551.7
1058.6
1566.0
2074.0
2582.5
3091.7
35101.5
40111.9
45123.1
50135.0
55147.6
60161.0
65175.3
70190.4
75206.4
80223.3
85241.1
90260.0
95279.9
100300.8
105322.8
110346.0
115370.4
120395.9
125422.8
130451.0
135481.0
140512.0
145545.0
150580.0

How to use this chart

The saturation curve shows the bubble-point pressure at which liquid R-454B begins to vaporize for a given temperature. In the field, you read this two ways:

  • Suction-side superheat: measure suction pressure → look up saturation temperature → subtract from the suction-line temperature. Open Superheat Calculator →
  • Liquid-side subcooling: measure liquid pressure → look up saturation temperature → subtract the liquid-line temperature. Open Subcool Calculator →

R-454B is a zeotropic blend with about 1.5 °F glide between bubble (saturated liquid) and dew (saturated vapor) points. This chart shows bubble-point pressures, which are the right reference for subcool work and within field tolerance for superheat. For tight superheat tuning, add ~1.5 °F when reading saturation temperature on the suction side.

R-454B is rated A2L (mildly flammable). Observe manufacturer leak, brazing, and ventilation requirements when servicing R-454B equipment. It is the lower-GWP successor to R-410A in modern residential and light commercial AC.

Data source: Honeywell / Chemours R-454B manufacturer datasheets (bubble-point pressures).