R-454B Pressure-Temperature Chart
Click the saturation curve, edit a value, or scan the table — every view stays in sync. Manufacturer-sourced bubble-point data for R-410A's lower-GWP successor.
For Licensed & Trained HVAC Technicians Only
This checklist is intended exclusively for use by licensed, certified, and trained HVAC professionals. It is not a DIY guide and should not be used by untrained individuals to perform repairs or diagnostics. The purpose of this checklist is to help qualified technicians maintain a consistent, step-by-step workflow so that no critical step is overlooked or skipped during service.
R-454B Saturation Curve
R-32 / R-1234yf (68.9 / 31.1 by mass, A2L) — zeotropic blend, ~1.5 °F glide
Click or tap anywhere on the chart — the cursor snaps to the R-454B saturation curve and stays there until your next click.
Direct Lookup
Edit either field — the other updates instantly. The chart cursor moves in sync.
Lookup Table
Tap any row to highlight that point on the chart.
| Temp (°F) | Pressure (psig) |
|---|---|
| 0 | 45.3 |
| 5 | 51.7 |
| 10 | 58.6 |
| 15 | 66.0 |
| 20 | 74.0 |
| 25 | 82.5 |
| 30 | 91.7 |
| 35 | 101.5 |
| 40 | 111.9 |
| 45 | 123.1 |
| 50 | 135.0 |
| 55 | 147.6 |
| 60 | 161.0 |
| 65 | 175.3 |
| 70 | 190.4 |
| 75 | 206.4 |
| 80 | 223.3 |
| 85 | 241.1 |
| 90 | 260.0 |
| 95 | 279.9 |
| 100 | 300.8 |
| 105 | 322.8 |
| 110 | 346.0 |
| 115 | 370.4 |
| 120 | 395.9 |
| 125 | 422.8 |
| 130 | 451.0 |
| 135 | 481.0 |
| 140 | 512.0 |
| 145 | 545.0 |
| 150 | 580.0 |
How to use this chart
The saturation curve shows the bubble-point pressure at which liquid R-454B begins to vaporize for a given temperature. In the field, you read this two ways:
- Suction-side superheat: measure suction pressure → look up saturation temperature → subtract from the suction-line temperature. Open Superheat Calculator →
- Liquid-side subcooling: measure liquid pressure → look up saturation temperature → subtract the liquid-line temperature. Open Subcool Calculator →
R-454B is a zeotropic blend with about 1.5 °F glide between bubble (saturated liquid) and dew (saturated vapor) points. This chart shows bubble-point pressures, which are the right reference for subcool work and within field tolerance for superheat. For tight superheat tuning, add ~1.5 °F when reading saturation temperature on the suction side.
R-454B is rated A2L (mildly flammable). Observe manufacturer leak, brazing, and ventilation requirements when servicing R-454B equipment. It is the lower-GWP successor to R-410A in modern residential and light commercial AC.
Data source: Honeywell / Chemours R-454B manufacturer datasheets (bubble-point pressures).